Re: E-Motor Start-Up Current
Erstellt am
1. Sep. 2009 - 02:58
Dear Alex,
The maximum current (disregarding the magnetic inrush current) is:
760/100 * 185 = 1406 Amps. at the initial scwitch on.
After the e-motor takes up speed, the consumed current decreases down to no load current at maximum rpm.
Can also be determined with the spreadsheet.
BR
Teus ■
Teus
Re: E-Motor Start-Up Current
Erstellt am
2. Sep. 2009 - 12:08
You may find this useful ...
http://www.abb.co.uk/product/seitp32...30034064f.aspx ■
E-motor Start-up Current
Hi All,
If we start an e-motor with the following characteristics with DOL method (with out any load, ie not connected to any load) what is the maximum current absorbed by the emotor in the start-up?
110 kW
locked rotor current : 760% of FL current
Full load current : 185 Amps ■