Dear Friends

I have 35m horizontal duct and i want use clean out opening according ACGIH fig. 5-24 but i don't understand why all of opening has angle and i think if my opening is under the duct is suitable ( (enclosed you will find my drawing of clean out opening))

what's your opinion?

what's your recommend about spacing of clean out door in horizontal duct?

if you know reference about design expansion joint and hood and duct support please introduce?

thanks in advance

Ohadi

Attachments

clean out opening (PDF)

Clean Out Door

Posted on 5. Jan. 2011 - 11:25

What process are you exhausting? What dust loading? Is the air moist?

A door in the bottom of the duct facilitates cleaning if you can hose out.

If you are expecting heavy dust build-up, space them at 6 m intervals.

If you design the system properly, according to ACGIH, there should be no need for cleaning.

Michael Reid.

Clean Out Door

Posted on 9. Jan. 2011 - 08:31
Quote Originally Posted by Michael ReidView Post
What process are you exhausting? What dust loading? Is the air moist?

A door in the bottom of the duct facilitates cleaning if you can hose out.

If you are expecting heavy dust build-up, space them at 6 m intervals.

If you design the system properly, according to ACGIH, there should be no need for cleaning.

Michael Reid.

thanks a lot for your response

Dust : Iron Ore

Relative Humidity: 70% max